120KVA UPS ABB Input/Output Cabinet incl. Maintenance Bypass 14-Circuit
120KVA UPS ABB Input/Output Cabinet incl. Maintenance Bypass 14-Circuit
ABB200ACabinet11-20-CircuitUPS input and output integrated cabinetUPS output cabinetUPS input cabinetStandard typeComputer Room
Bill of materials
| Category | Brand | Product | Dimensions | Weight | Qty | |
|---|---|---|---|---|---|---|
| Enclosure | Totem | Rack W600*H2000*D1000 | 600*2000*1000 | 35 | 1 | |
| Moulded Case Distribution Breaker | ABB | T3N250 TMD200/2000 FFCL 4P N=100%(10055892+10151958) | - | 0 | 1 | |
| Miniature Circuit Breaker (MCB) | ABB | S204-C63 | - | 0 | 4 | |
| Miniature Circuit Breaker (MCB) | ABB | S204-C32 | - | 0 | 1 | |
| Moulded Case Distribution Breaker | ABB | XT3N250 TMD200-2000 FFCL 3P (10152694+10151925) | - | 0 | 1 | |
| Moulded Case Distribution Breaker | ABB | T1N160 TMD160/1600 FFC 3P | - | 0 | 1 | |
| Moulded Case Distribution Breaker | ABB | XT1N160 TMD100-1000 FF 3P | - | 0 | 1 | |
| Miniature Circuit Breaker (MCB) | ABB | S202-C63 | - | 0 | 3 | |
| Miniature Circuit Breaker (MCB) | ABB | S202-C32 | - | 0 | 2 | |
| Miniature Circuit Breaker (MCB) | ABB | S202-C16 | - | 0 | 4 | |
| Meter | Domestic high quality | 1-Phase Power Meter AMC72L-E/KC | - | 0 | 1 | |
| Instrument Transformer | CHINT | BH-0.66 200/5A | 30 | 0 | 3 | |
| Copper Busbar | National standard | Copper busbar | - | 0 | 12 | |
| Surge Protection | ABB | POD T2 80/35/4 | - | 0 | 2 | |
| Total | 35 | 37 |